TRIO PS 1AC 24DC 10A Power Supply Phoenix Contact
Phoenix Contact TRIO PS 1AC 24DC 10A :
Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/10 A
Specification :
Dimensions
Width |
60 mm |
Height |
130 mm |
Depth |
152.5 mm |
Back to top
Ambient conditions
Degree of protection |
IP20 |
Ambient temperature (operation) |
-25 °C … 70 °C (> 55° C derating : 2.5%/K) |
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
Climatic class |
3K3 (in acc. with EN 60721) |
Degree of pollution |
2 |
Back to top
Input data
Nominal input voltage range |
100 V AC … 240 V AC |
Input voltage range |
85 V AC … 264 V AC (Derating < 90 V AC: 2,5 %/V) |
Dielectric strength maximum |
300 V AC |
AC frequency range |
45 Hz … 65 Hz |
Discharge current to PE |
< 3.5 mA |
Current consumption |
3 A (100 V AC) |
|
1.5 A (240 V AC) |
Nominal power consumption |
272 VA |
Inrush surge current |
< 15 A |
Mains buffering |
> 24 ms (120 V AC) |
|
> 24 ms (230 V AC) |
Input fuse |
6.3 A (slow-blow, internal) |
Choice of suitable circuit breakers |
10 A … 16 A (Characteristics B, C, D, K) |
Power factor (cos phi) |
0.99 |
Type of protection |
Transient surge protection |
Protective circuit/component |
Varistor |
Back to top
Output data
Nominal output voltage |
24 V DC ±1 % |
Setting range of the output voltage (USet) |
22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
Nominal output current (IN) |
10 A (UOUT = 24 V DC) |
Derating |
55 °C … 70 °C (2.5%/K) |
Connection in parallel |
Yes, for redundancy and increased capacity |
Connection in series |
yes |
Feedback resistance |
35 V DC |
Protection against surge voltage on the output |
< 35 V DC |
Max. capacitive load |
Unlimited |
Active current limitation |
Approx. 14 A (for short-circuit) |
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 2 % (change in load, dynamic 10 % … 90 %) |
|
< 0.1 % (change in input voltage ±10 %) |
Residual ripple |
< 10 mVPP |
Output power |
240 W |
Typical response time |
< 1 s |
Peak switching voltages nominal load |
< 50 mVPP |
Maximum power dissipation in no-load condition |
6.7 W |
Power loss nominal load max. |
30 W |
Back to top
General
Net weight |
1.4 kg |
Operating voltage display |
Green LED |
Efficiency |
89 % (for 230 V AC and nominal values) |
Insulation voltage input/output |
4 kV AC (type test) |
|
2 kV AC (routine test) |
Insulation voltage input / PE |
2 kV AC (type test) |
|
2 kV AC (routine test) |
Insulation voltage output / PE |
500 V DC (type test) |
Protection class |
I (with PE connection) |
Degree of protection |
IP20 |
MTBF (IEC 61709, SN 29500) |
> 981000 h (40 °C) |
Mounting position |
horizontal DIN rail NS 35, EN 60715 |
Assembly instructions |
alignable: horizontally 0 mm, vertically 50 mm |
Back to top
Connection data, input
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
14 |
Stripping length |
9 mm |
Screw thread |
M2,5 |
Back to top
Connection data, output
Connection method |
Screw connection |
Conductor cross section solid min. |
0.2 mm² |
Conductor cross section solid max. |
2.5 mm² |
Conductor cross section flexible min. |
0.2 mm² |
Conductor cross section flexible max. |
2.5 mm² |
Conductor cross section AWG min. |
24 |
Conductor cross section AWG max. |
14 |
Stripping length |
9 mm |
Screw thread |
M2,5 |
Back to top
Signaling
Status display |
“DC OK” LED green |
Note on status display |
UOUT < 0.9 x UN: LED flashing |
Back to top
Standards and Regulations
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
Noise immunity |
EN 61000-6-2:2005 |
Connection in acc. with standard |
CUL |
Standards/regulations |
EN 61000-4-2 |
Contact discharge |
4 kV (Test Level 2) |
Standards/regulations |
EN 61000-4-3 |
Frequency range |
80 MHz … 1 GHz |
Test field strength |
10 V/m |
Frequency range |
1.4 GHz … 2 GHz |
Test field strength |
3 V/m |
Standards/regulations |
EN 61000-4-4 |
Comments |
Criterion B |
Standards/regulations |
EN 61000-6-3 |
|
EN 61000-4-6 |
Frequency range |
0.15 MHz … 80 MHz |
Voltage |
10 V (Test Level 3) |
Standards/regulations |
EN 61000-4-11 |
Low Voltage Directive |
Conformance with LV directive 2006/95/EC |
Standard – Electrical safety |
EN 60950-1/VDE 0805 (SELV) |
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations |
EN 50178/VDE 0160 (PELV) |
Standard – Safety extra-low voltage |
EN 60950-1 (SELV) |
|
EN 60204 (PELV) |
Standard – Safe isolation |
DIN VDE 0100-410 |
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment |
EN 50178 |
Standard – Limitation of mains harmonic currents |
EN 61000-3-2 |
UL approvals |
UL/C-UL listed UL 508 |
|
UL/C-UL Recognized UL 60950-1 |
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz … 150 Hz, 2.3g, 90 min. |
Back to top
Environmental Product Compliance
China RoHS |
Environmentally Friendly Use Period = 25; |
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration” |
Back to to
Download Manual