Call:- 01670-070357 to repair your industrial electronics items.

Phoenix Contact TRIO PS 1AC 24DC 10A

Availability:

Out of stock


Phoenix Contact Trio-Ps/1Ac/24Dc/10 Power Supply Input 100-240V Output 24V / 10A

Brand: Phoenix Contact
Model: TRIO PS 1AC 24DC 10A
Specification: Input: 100-240V/ 3-1.5A/ 50-60 Hz, Operational Voltage: 85-264V,  Derating: <90V-2.5%/V, Output: 24V/10A
Condition: Used/Refurbished
Origin: Germany

Warranty: Three months.

Download Manual
Show Other Products
Call us at +88 01670070357

Call for Repair

TRIO PS 1AC 24DC 10A Power Supply Phoenix Contact

Phoenix Contact TRIO PS 1AC 24DC 10A :

Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/10 A

Specification :

Dimensions

Width 60 mm
Height 130 mm
Depth 152.5 mm

Back to top

Ambient conditions

Degree of protection IP20
Ambient temperature (operation) -25 °C … 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Max. permissible relative humidity (operation) ≤ 95 % (at 25 °C, non-condensing)
Climatic class 3K3 (in acc. with EN 60721)
Degree of pollution 2

Back to top

Input data

Nominal input voltage range 100 V AC … 240 V AC
Input voltage range 85 V AC … 264 V AC (Derating < 90 V AC: 2,5 %/V)
Dielectric strength maximum 300 V AC
AC frequency range 45 Hz … 65 Hz
Discharge current to PE < 3.5 mA
Current consumption 3 A (100 V AC)
1.5 A (240 V AC)
Nominal power consumption 272 VA
Inrush surge current < 15 A
Mains buffering > 24 ms (120 V AC)
> 24 ms (230 V AC)
Input fuse 6.3 A (slow-blow, internal)
Choice of suitable circuit breakers 10 A … 16 A (Characteristics B, C, D, K)
Power factor (cos phi) 0.99
Type of protection Transient surge protection
Protective circuit/component Varistor

Back to top

Output data

Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (UOUT = 24 V DC)
Derating 55 °C … 70 °C (2.5%/K)
Connection in parallel Yes, for redundancy and increased capacity
Connection in series yes
Feedback resistance 35 V DC
Protection against surge voltage on the output < 35 V DC
Max. capacitive load Unlimited
Active current limitation Approx. 14 A (for short-circuit)
Control deviation < 1 % (change in load, static 10 % … 90 %)
< 2 % (change in load, dynamic 10 % … 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple < 10 mVPP
Output power 240 W
Typical response time < 1 s
Peak switching voltages nominal load < 50 mVPP
Maximum power dissipation in no-load condition 6.7 W
Power loss nominal load max. 30 W

Back to top

General

Net weight 1.4 kg
Operating voltage display Green LED
Efficiency 89 % (for 230 V AC and nominal values)
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage input / PE 2 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (type test)
Protection class I (with PE connection)
Degree of protection IP20
MTBF (IEC 61709, SN 29500) > 981000 h (40 °C)
Mounting position horizontal DIN rail NS 35, EN 60715
Assembly instructions alignable: horizontally 0 mm, vertically 50 mm

Back to top

Connection data, input

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5

Back to top

Connection data, output

Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 9 mm
Screw thread M2,5

Back to top

Signaling

Status display “DC OK” LED green
Note on status display UOUT < 0.9 x UN: LED flashing

Back to top

Standards and Regulations

Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
Noise immunity EN 61000-6-2:2005
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
Contact discharge 4 kV (Test Level 2)
Standards/regulations EN 61000-4-3
Frequency range 80 MHz … 1 GHz
Test field strength 10 V/m
Frequency range 1.4 GHz … 2 GHz
Test field strength 3 V/m
Standards/regulations EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-6-3
EN 61000-4-6
Frequency range 0.15 MHz … 80 MHz
Voltage 10 V (Test Level 3)
Standards/regulations EN 61000-4-11
Low Voltage Directive Conformance with LV directive 2006/95/EC
Standard – Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage EN 60950-1 (SELV)
EN 60204 (PELV)
Standard – Safe isolation DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment EN 50178
Standard – Limitation of mains harmonic currents EN 61000-3-2
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz … 150 Hz, 2.3g, 90 min.

Back to top

Environmental Product Compliance

China RoHS Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer’s declaration”

Back to to

Download Manual
Show Other Products

SKU: 5361 Category:
Call Now Button