Siemens Simatic HMI KTP600 basic mono pn 6AV6 647 0AB11 3AX0 , Basic Panel, Key / touch operation, 6 “STN display, 4 gray levels, PROFINET interface, configurable as of WinCC flexible 2008 SP2 Compact / WinCC Basic V10.5 / STEP 7 Basic V10.5, contains open-source software, which is free of charge.
Specifications :
General information | ||
Product type designation | KTP Basic mono PN | |
display | ||
Design of display | STN | |
Screen diagonal | 5.7 in | |
Display width | 115.2 mm | |
Display height | 86.4 mm | |
Number of colors | 4; Gray Scales | |
Resolution (pixels) | ||
● Horizontal image resolution | 320 pixels | |
● Vertical image resolution | 240 pixels | |
Backlighting | ||
● MTBF backlighting (at 25 ° C) | 50,000 h | |
● Backlight dimmable | No | |
Control elements | ||
Keyboard fonts | ||
● Function keys | ||
– Number of function keys | 6 | |
● Keys with LED | No | |
● System keys | No | |
● Numeric keyboard | Yes; Onscreen keyboard | |
● alphanumeric keyboard | Yes; Onscreen keyboard | |
Touch operation | ||
● Design as touch screen | Yes | |
Installation type / mounting | ||
Mounting position | vertical | |
Mounting in portrait format possible | Yes | |
Mounting in landscape format possible | Yes | |
maximum permissible angle of inclination without external ventilation | 35 ° | |
Supply voltage | ||
Type of supply voltage | DC | |
Rated value (DC) | 24V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
Current consumption | 0.24 A | |
Starting current inrush I²t | 0.5 A² · s | |
power | ||
Active power input, typ. | 6 W | |
Processor | ||
Processor type | RISC 32 bit | |
Memory | ||
Flash | Yes | |
R.A.M. | Yes | |
Memory available for user data | 1 Mbyte | |
Type of output | ||
Acoustics | ||
● Buzzer | Yes | |
● Speaker | No | |
Time of day | ||
Clock | ||
● Hardware clock (real-time) | No | |
● Software clock | Yes | |
● Retentive | No | |
● synchronizable | Yes | |
interfaces | ||
Number of industrial Ethernet interfaces | 1 | |
Number of RS 485 interfaces | 0 | |
Number of RS 422 interfaces | 0 | |
Number of RS232 interfaces | 0 | |
Number of USB interfaces | 0 | |
Number of 20 mA interfaces (TTY) | 0 | |
Number of parallel interfaces | 0 | |
Number of other interfaces | 0 | |
Number of SD card slots | 0 | |
With software interfaces | No | |
Industrial Ethernet | ||
● Industrial Ethernet status LED | 2 | |
Protocols | ||
PROFINET | Yes | |
Support protocol for PROFINET IO | No | |
IRT | No | |
PROFIBUS | No | |
MPI | No | |
Protocols (Ethernet) | ||
● TCP / IP | Yes | |
● DHCP | Yes | |
● SNMP | Yes | |
● DCP | Yes | |
● LLDP | Yes | |
WEB characteristics | ||
● HTTP | No | |
● HTML | No | |
Further protocols | ||
● CAN | No | |
● EtherNet / IP | Yes | |
● MODBUS | Yes; Modicon (MODBUS TCP / IP) | |
Interrupts / diagnostics / status information | ||
Diagnostic messages | ||
● Diagnostic information readable | No | |
Degree and class of protection | ||
IP (at the front) | IP65 | |
Enclosure Type 4 at the front | Yes | |
Enclosure Type 4x at the front | Yes | |
IP (rear) | IP20 | |
Standards, approvals, certificates | ||
CE mark | Yes | |
cULus | Yes | |
RCM (formerly C-TICK) | Yes | |
KC approval | Yes | |
Use in hazardous areas | ||
● ATEX Zone 2 | No | |
● ATEX Zone 22 | No | |
● cULus Class I Zone 1 | No | |
● cULus Class I Zone 2, Division 2 | No | |
● FM Class I Division 2 | No | |
Marine approval | ||
● Germanischer Lloyd (GL) | Yes | |
● American Bureau of Shipping (ABS) | Yes | |
● Bureau Veritas (BV) | Yes | |
● Det Norske Veritas (DNV) | Yes | |
● Lloyd’s Register of Shipping (LRS) | Yes | |
● Nippon Kaiji Kyokai (Class NK) | Yes | |
● Polski Rejestr Statkov (PRS) | Yes | |
Ambient conditions | ||
Ambient temperature during operation | ||
● Operation (vertical installation) | ||
– For vertical installation, min. | 0 ° C | |
– For vertical installation, max. | 50 ° C | |
● Operation (max tilt angle) | ||
– At maximum tilt angle, min. | 0 ° C | |
– At maximum tilt angle, min. | 40 ° C | |
● Operation (vertical installation, portrait format) | ||
– For vertical installation, min. | 0 ° C | |
– For vertical installation, max. | 50 ° C | |
● Operation (max tilt angle, portrait format) | ||
– At maximum tilt angle, min. | 0 ° C | |
– At maximum tilt angle, min. | 40 ° C | |
Ambient temperature during storage / transportation | ||
● min. | -20 ° C | |
● max. | 60 ° C | |
Relative humidity | ||
● Operation, max. | 90%; no condensation | |
Operating systems | ||
proprietary | Yes | |
pre-installed operating system | ||
● Windows CE | No | |
Configuration | ||
Message indicator | Yes | |
Alarm system (including buffer and acknowledgment) | Yes | |
Process value display (output) | Yes | |
Process value default (input) possible | Yes | |
Recipe management | Yes | |
Configuration software | ||
● STEP 7 Basic (TIA Portal) | Yes; via integrated WinCC Basic (TIA Portal) | |
● STEP 7 Professional (TIA Portal) | Yes; via integrated WinCC Basic (TIA Portal) | |
● WinCC flexible Compact | Yes | |
● WinCC flexible standard | Yes | |
● WinCC flexible Advanced | Yes | |
● WinCC Basic (TIA Portal) | Yes | |
● WinCC Comfort (TIA Portal) | Yes | |
● WinCC Advanced (TIA Portal) | Yes | |
● WinCC Professional (TIA Portal) | Yes | |
Languages | ||
Online languages | ||
● Number of online / runtime languages | 5 | |
Project languages | ||
● Languages per project | 32 | |
Functionality under WinCC (TIA Portal) | ||
Libraries | Yes | |
Task planner | ||
● time-controlled | No | |
● task-controlled | Yes | |
Help system | ||
● Number of characters per info text | 320 | |
Message system | ||
● Number of alarm classes | 32 | |
● Bit messages | ||
– Number of bit messages | 200 | |
● Analog messages | ||
– Number of analog messages | 15 | |
● System messages HMI | Yes | |
● Number of characters per message | 80 | |
● Number of process values per message | 8th | |
● Message indicator | Yes | |
● Message buffer | ||
– Number of entries | 256 | |
– Circulating buffer | Yes | |
– Retentive | Yes | |
– maintenance-free | Yes | |
Recipe management | ||
● Number of recipes | 5 | |
● Data records per recipe | 20 | |
● Entries via data record | 20 | |
● Size of internal recipe memory | 40 kbytes | |
● Recipe memory expandable | No | |
Variables | ||
● Number of variables per device | 500 | |
● Number of variables per screen | 30 | |
● Limit values | Yes | |
● multiplexing | Yes | |
● Structures | No | |
● Arrays | Yes | |
Images | ||
● Number of configurable images | 50 | |
● Permanent window / default | Yes | |
● Global image | Yes | |
● Image selection by PLC | Yes | |
● Image number in the PLC | Yes | |
Image objects | ||
● Number of objects per image | 30 | |
● Text fields | Yes | |
● I / O fields | Yes | |
● Graphic I / O fields (graphics list) | Yes | |
● Symbolic I / O fields (text list) | Yes | |
● Date / time fields | Yes | |
● switches | Yes | |
● Buttons | Yes | |
● Graphic display | Yes | |
● Icons | Yes | |
● Geometric objects | Yes | |
Complex image objects | ||
● Number of complex objects per screen | 5 | |
● Alarm view | Yes | |
● Trend view | Yes | |
● User view | Yes | |
● Status / control | No | |
● Sm @ rtClient view | No | |
● Recipe view | Yes | |
● f (x) trend view | No | |
● System diagnostics view | No | |
● Media player | No | |
● Bar graphs | Yes | |
● Sliders | No | |
● pointer instruments | No | |
● Analogue / digital clock | No | |
Lists | ||
● Number of text lists per project | 150 | |
● Number of entries per text list | 30 | |
● Number of graphics lists per project | 100 | |
● Number of entries per graphics list | 30 | |
Archiving | ||
● Number of archives per device | 0 | |
Security | ||
● Number of user groups | 50 | |
● Number of user rights | 32 | |
● Number of users | 50 | |
● Password export / import | No | |
● SIMATIC Logon | No | |
Character sets | ||
● Keyboard fonts | ||
– US English | Yes | |
Transfer (upload / download) | ||
● MPI / PROFIBUS DP | No | |
● USB | No | |
● Ethernet | Yes | |
● using external storage medium | No | |
Process coupling | ||
● S7-1200 | Yes | |
● S7-1500 | Yes | |
● S7-200 | Yes | |
● S7-300 / 400 | Yes | |
● LOGO! | Yes | |
● WinAC | Yes | |
● SINUMERIK | No | |
● SIMOTION | No | |
● Allen Bradley (EtherNet / IP) | Yes | |
● Allen Bradley (DF1) | No | |
● Mitsubishi (MC TCP / IP) | Yes | |
● Mitsubishi (FX) | No | |
● OMRON (FINS TCP) | No | |
● OMRON (LINK / Multilink) | No | |
● Modicon (Modbus TCP / IP) | Yes | |
● Modicon (Modbus) | No | |
Service tools / configuration aids | ||
● Backup / Restore manually | Yes | |
● Backup / Restore automatically | No | |
● Simulation | Yes | |
● Device switchover | Yes | |
Peripherals / Options | ||
Peripherals | ||
● Printer | No | |
● SIMATIC HMI MM memory card: Multi Media Card | No | |
● SIMATIC HMI SD Memory Card: Secure Digital Memory Card | No | |
● USB memory | No | |
Mechanics / material | ||
Enclosure material (front) | ||
● Plastic | Yes | |
● Aluminum | No | |
● Stainless steel | No | |
Dimensions | ||
Width of the housing front | 214 mm | |
Height of housing front | 158 mm | |
Mounting cutout, width | 197 mm | |
Mounting cutout, height | 141 mm | |
Overall depth | 44 mm | |
weights | ||
Weight without packaging | 1.07 kg | |
Weight incl. Packaging | 1.3 kg | |